460MSBS - Protocol Gateway Product User Guide Software Build Date: January 15th, 2015 Revision 3 Real Time Automation, Inc. 1 1-800-249-1612

Pagina 2

Main Page The main page is where important information about your gateway and its connections are displayed. Mode (orange box below): Running Mode

Pagina 3

Device Configuration The device configuration area is where you assign the device description, IP address, and other network parameters. Changes can

Pagina 4

Modbus TCP/IP Server Configuration Click the Modbus TCP/IP Server button to access the configuration page. 1) Enter a Device Label to identify the d

Pagina 5 - Overview

Modbus TCP/IP Server Configuration-Data Groups The bottom area of the Modbus TCP/IP Server Configuration page lets you configure up to 100 Data Group

Pagina 6 - Required Tools and Data

Modbus TCP/IP Server Data Group Configuration: Auto-Server Mode (Default) While in Auto-Server mode the # of data groups and the actual data groups t

Pagina 7

Modbus TCP/IP Server Data Group Configuration: Manual Mode 1. Click the Edit Data Groups button to switch from Auto-Server Mode to Manual Mode. Once

Pagina 8 - Accessing the Main Page

This means that Register 1 will hold the length of the string and Registers 2-5 will hold the string contents. This string can contain a max of 8 cha

Pagina 9

BACnet/IP Server Configuration Click the BACnet/IP Server button to access the primary configuration page for this device. 1) Enter a Device Label.

Pagina 10 - Main Page

BACnet/IP Server Configuration-Data Groups The bottom area of the BACnet/IP Server Configuration page lets you configure multiple objects for Read an

Pagina 11 - Device Configuration

BACnet/IP Server Configuration: Auto-Server Mode (Default) While in Auto-Server mode no fields under the Data Groups can be edited. Auto-Server Mode

Pagina 12

Trademarks CompactLogix, ControlLogix, & PLC-5 are registered trademarks of Rockwell Automation, Inc. EtherNet/IP is a trademark of the ODVA. Mic

Pagina 13

BACnet/IP Server Object Configuration – Analog Objects Click the Set Up BACnet Names, Units, and COV button at the bottom of the BACnet/IP Server Con

Pagina 14 - (Default)

BACnet/IP Server Object Configuration – Binary Objects Click the Set Up BACnet Names, Units, and COV button at the bottom of the BACnet/IP Server Con

Pagina 15

BACnet/IP Server Object Configuration – CharacterString Value Objects Click the Set Up BACnet Names, Units, and COV button at the bottom of the BACne

Pagina 16

BACnet/IP Server Object Configuration – Group Names Click the Set Up BACnet Names, Units, and COV button at the bottom of the Advanced BACnet/IP Serv

Pagina 17

BACnet/IP Server Routing Configuration Click the Set Up Static Device Binding and Foreign Device registration button at the bottom of the BACnet/IP S

Pagina 18

Mapping - Transferring Data between Devices There are 5 ways to move data from one protocol to the other. You can combine any of the following option

Pagina 19

Display Mapping and Values The Display Data and Display String pages are where you can view the actual data for each mapping that is set up. Displa

Pagina 20

If there are values of “- -“ on this page, it indicates that the source has not yet been validated and no data is being sent to the destination. Th

Pagina 21

Display String Click the Display String button to view how the string data types are mapped and what the values of each string are. Here you will se

Pagina 22 - Objects

Data and String Mapping – Auto-Map The Auto-Map function looks at both of the protocols and will map the data between the two protocols as best as it

Pagina 23

Overview ...

Pagina 24

Data Mapping – Explanation Below are the different parts that can be modified to make up a data mapping. 1. Enable (red box above): Check to enable

Pagina 25

Data Mapping – Adding Diagnostic Information Data Mapping offers 5 different types of information in addition to any scan lines specified for each pr

Pagina 26 - Display Data

may be beneficial to know if a Server/Slave device is down. By using this Network Bitmap Status you can expose the connection statuses of individual

Pagina 27

Recoverable Faults: 0x00FF0000 (bit 16-23)3rd byte Hex: Bit Position: Decimal: Explanation: 0x01 16 65,536 recoverable fault -

Pagina 28 - Display String

String Mapping – Explanation Below are the different parts that can be modified to make up a string mapping. String data types can only be mapped to

Pagina 29

Mapping – Auto-Map Mode to Manual-Map Mode To transition from Auto-Map mode to Manual-Map mode, click the Edit Mapping button. After you click this b

Pagina 30 - Data Mapping – Explanation

Mapping – Manual-Map Mode to Auto-Map Mode To transition from Manual-Map mode to Auto-Map mode, click the Auto Map Mode button. After you click this

Pagina 31

View Data Mapping as Text The View as Text page displays the point to point mapping(s) you set up in the Data Mapping section. This will also display

Pagina 32

View String Mapping as Text The View as Text page displays the string mapping(s) you set up in the String Mapping section. Each line on this page wi

Pagina 33

Security Configuration You can configure Security for 3 administrators, 5 users, and 1 guest. Note: Only Admins have configuration access to all we

Pagina 35

Security Configuration-Security Levels Each webpage in our gateway can have a separate security level associated with it for each user. Security Lev

Pagina 36

Security - Log In Username: Name of the user to login. Password: Password of the user to login. Log In: If login is successful, the user will be redi

Pagina 37 - View Data Mapping as Text

Security - Log Out Once a user is done with a session they may click logout at the top of any page. The user may also be logged out for inactivity ba

Pagina 38 - View String Mapping as Text

Email Configuration You can configure up to 10 email addresses. 1. SMTP Mail Username: The email address that the smtp server has set up to use. 2

Pagina 39 - Security Configuration

Alarm Configuration 1. Alarm Delay upon Powerup: At Powerup, the gateway will have values of ‘0’ stored for all data. This may cause alarms to trigg

Pagina 40

5. In the Clear Error Section: a. Select the Clear Error Operation. Available options are <, >, <=, >=, !=, ==, and Change of State (

Pagina 41 - Security - Log In

Diagnostics – Alarm Status Alarm Status will only display under the Diagnostic menu tab if at least 1 Alarm is enabled. 1. # Alarms Enabled: This is

Pagina 42 - Security - Log Out

Alarms – Clear When an alarm is cleared, the following will occur: 1. A one-time notification will be sent to the email associated with the alarm

Pagina 43 - Email Configuration

Change of State (COS) Configuration The gateway, by default only writes when data has changed. The gateway also waits to write any data to the destin

Pagina 44 - Alarm Configuration

Diagnostics Info The Diagnostic page is where you will be able view the gateway’s translations and protocol specific status information. For protocol

Pagina 45

Overview The 460MSBS gateway connects a Modbus TCP Client device to a BACnet/IP Client. By following this guide, you will be able to configure the 46

Pagina 46 - Alarms – Active

Diagnostics – Modbus TCP/IP Server Select the Modbus TCP/IP Server in the dropdown menu on the Diagnostic. Additional diagnostic information can be

Pagina 47 - Alarms – Clear

Diagnostics – Modbus TCP/IP Server LED Status: 1. Good Communication (Solid Green) – The gateway is connected to a Modbus TCP/IP Client and communic

Pagina 48

Diagnostics – BACnet/IP Server Select the BACnet/IP Server in the drop down menu on the Diagnostic page. Additional diagnostic information can be f

Pagina 49 - Diagnostics Info

Variables: 1. Total Msg Request Count – Total Number of Messages Received from the BACnet/IP Client. 2. Read Property Request Received – Number of

Pagina 50

c. “Invalid Tag” – BACnet/IP message is not how the gateway expects the message. d. “Parameter Out of Range” – The BACnet/IP Client is asking for

Pagina 51

LED Configuration To modify the behavior of the LEDs on the 460 gateway, navigate to Other->Setup LEDs. The LED Configuration page lets you config

Pagina 52

Configuration Files To access the configuration files in the 460 gateway, navigate to other->Export/Import Config. Export Configuration The expor

Pagina 53

Utilities The Utilities screen displays information about the gateway including Operation Time, File System Usage, Memory Usage, and Memory Block Usa

Pagina 54

Completing the Installation You have now set up your gateway for communication and are ready to place the device in your application. Support for yo

Pagina 55 - LED Configuration

Required Tools and Data You will need the following tools: The gateway The provided CD-ROM o IPSetup.exe can also be downloaded: http://www.rt

Pagina 56 - Import Configuration

Powering The Gateway The following steps will allow you to properly and safely power the gateway. 1. Connect a 24VDC power source to the gateway

Pagina 57 - Utilities

Accessing the Main Page The following steps will allow you to connect to the browser based configuration of the gateway. 1. Using the supplied cr

Pagina 58 - Completing the Installation

Error: Main Page Does Not Launch If the Main Page does not launch please verify the following: 1. Check that the PC is set for a Static IP Address a